1) Chemical (water treatment room) 5 L/s pp plus 0.9 L/s m2 (plus 30% LEED)
2) Gas suppression room 5 L/s pp plus 0.9 L/s m2 (plus 30% LEED)
3) Shipping and receiving area 5 L/s pp plus 0.6 L/s m2 (plus 30% LEED)
4) Packing light assembly 3.8 L/s pp plus 0.6 L/s m2 (plus 30% LEED)
5) Computer lab/data room 5 L/s pp plus 0.6 L/s m2 (plus 30% LEED)
6) Laboratories 5 L/s pp plus 0.9 L/s m2 (plus 30% LEED)
7) Kitchen 3.8 L/s pp plus 0.6 L/s m2 (plus 30% LEED)
8) Corridors 0.3 L/s m2 (plus 30% LEED)
9) Meeting room 2.5 L/s pp plus 0.3 L/s m2 (plus 30% LEED)
or 10 L/s pp (whichever is highest)
10) Office 2.5 L/s pp plus 0.3 L/s m2 (plus 30% LEED)
or 10 L/s pp (whichever is highest)
11) Restrooms/toilet 50 m3/h
12) Showers 75 m3/h
各场所噪声级参数
a. Maximum equivalent sound pressure level LA,eq from installations
1) Office areas 45 dB(A)
2) Meeting rooms 35 dB(A)
3) Computer rooms 80 dB(A)
4) Applied office areas 45 dB(A)
5) General office 50 dB(A)
6) Shops 60 dB(A)
7) Commercial warehouse 60 dB(A)
8) Restaurants 45 dB(A)
b. Outdoor* (industrial areas, maximum noise levels at the boundary
1) Maximum equivalent sound pressure level LA,eq
(a) Daytime 70 dB(A)
(b) Evening 65 dB(A)
(c) Night 60 dB(A)
2) *From noise source of the electrical/mechanical equipment till to the property
boundary of the plot
声明:本站部分文章内容及图片转载于互联 、内容不代表本站观点,如有内容涉及侵权,请您立即联系本站处理,非常感谢!